You are only a click away from a Titus solution.

Role Based Solutions
Frequently Asked Questions
Titus Document Index
Search Representative

ARI 885-98 Update

ARI Standard 885 is the “Standard for Estimating Occupied Space Sound Levels in the Applications of Air Terminals and Air Outlets”. The standard was developed by the Air-Conditioning and Refrigeration Institute (ARI) to establish a uniform industry procedure for estimating sound pressure levels in occupied spaces served by air terminals and/or air outlets. ARI 885 establishes consistent, industry-accepted practices for calculating room sound pressures used to determine the Noise Criteria (NC) of a terminal in a space.

ARI 885-98, as amended by the 2002 Addendum, includes Appendix E which specifies the sound attenuation values for diffuser sound, air terminal discharge sound, and air terminal radiated sound. As of April 2003, all manufacturers are required to publish NC ratings based on ARI 885-98.

Specifically, the standard requires manufacturers to use a 10dB room absorption deduction for diffusers, Type 2 mineral fiber ceiling deducts for terminal radiated sound, and one of three sets of deducts based on CFM for terminal discharge sound.

Many in the industry believed the previous standard, ARI 885-90, was too generous in its attenuation allowances for terminals. ARI reviewed the standard and introduced more accurate attenuation factors in 885-98. The updated allowances are reduced from the previous standard, which will effectively increase the NC rating of any given terminal when compared to the NC rating using the previous standard, ARI 885-90.

The primary changes ARI 885-98 are as follows:

ASHRAE research determined that noise sources above a suspended ceiling should be classified as an area source, not a point source as it was in ARI 885-90. ARI developed a new table used for radiated sound based on a fixed room volume and receiver distance. This new table for Ceiling/Space Effect, based on ceiling type, has decreased attenuation factors than the combined Ceiling and Space Effect tables of 885-90.

The Environmental Adjustment Factor was decreased in ARI 885-98. The table below shows the current and previous Environmental Adjustment Factor.

Octave Band 2 3 4 5 6 7
ARI 885-90 Environmental Adj. 3 2 1 1 1 1
ARI 885-98 Environmental Adj. 2 1 0 0 0 0

The calculation for determining end reflection loss changed in ARI 885-98. The sudden area change at the exit of an integral terminal unit or outlet can reflect significant low frequency energy back into the attached ductwork. This is end reflection loss. The calculation change resulted in a reduction in the attenuation credit for end reflection.

The following table shows the ARI 885-98 attenuation allowance compared to ARI 885-90 allowance:

Octave Bands
2 3 4 5 6 7
Radiated Sound Allowance Change -1 -2 -4 -1 +2 +6
Discharge Sound Allowance Change -5 -5 -2 -4 -3 -3

The average change between the two standards represents a 4 to 6 NC increase in application data. The following tables show the difference between ARI 885-90 and ARI 885-98 for the same sound power data.

Radiated Sound Attenuation Octave Bands NC
2 3 4 5 6 7
Unit Catalog Sound Power 69 64 60 55 48 42
ARI 885-90 Room Sound Pressure 48 42 36 28 19 12 32
ARI 885-98 Room Sound Pressure 49 44 40 29 17 6 35

Discharge Sound Attenuation Octave Bands NC
2 3 4 5 6 7
Unit Catalog Sound Power 73 69 65 62 62 61
ARI 885-90 Room Sound Pressure 43 38 26 9 9 22 26
ARI 885-98 Room Sound Pressure 48 43 28 13 12 25 33

For equal sound power data, NC ratings cataloged to ARI 885-98 will be higher than previous cataloged data, but will reflect a more realistic sound performance in the field. However, Titus recently introduced an improved flow sensor, the AeroCrossTM, which has significantly reduced the terminals ambient noise generation. The net result of reporting to the new standard and the changeover to the AeroCrossTM is that some NC ratings have increased, while some ratings have decreased compared to past catalogs.